GF Signet 3-2750-2 In-line Sensor Electronics with EasyCal (yellow body) - recommended for 4 to 20
In-line Sensor Electronics with EasyCal (yellow body) - recommended for 4 to 20 for process monitoring and control
GF Signet 3-2750-2 is the In-line Sensor Electronics with EasyCal (yellow body) - recommended for 4 to 20 for process monitoring and control.
GF Signet 3-2750-2 In-line Sensor Electronics with EasyCal (yellow body) - recommended for 4 to 20
GF Signet 3-2750-2 is the In-line Sensor Electronics with EasyCal (yellow body) - recommended for 4 to 20 for process monitoring and control.
Specifications and Features
Signet 2750 DryLoc® pH/ORP Sensor Electronics
The Signet 2750 pH/ORP Sensor Electronics featuring the DryLoc® connector, provides a variety of functions to suit various requirements. The 2750 has a preamplified signal and features two different outputs: a two wire 4 to 20 mA loop output with EasyCal function or a digital (S3 L) output which allows for longer cable lengths and is compatible with the Signet 8900 Multi-Parameter Controller. The 2750 self-configures for pH or ORP operation via automatic recognition of the electrode type. The optional EasyCal feature allows simple push-button calibration and includes an LED indicator for visual feedback. The DryLoc® electrode connector quickly forms a robust assembly for submersible and in-line installations. NEMA 4X junction enclosures are integral parts of the 2750 in-line version and are also available as accessories for the submersible 2750. The 2750 submersible preamplifier can also be used as an In-line preamplifier when used with the 3/4” or 1” threaded sensors including the 2724, 2774 and 2764 series electrodes. The 2750 in-line preamplifier can be used with Signet fittings up to DN100 (4 in.) and wet-tap assemblies.
Fields of Application:
- Water/Wastewater Treatment
- Neutralization Systems
- Scrubber Control
- Effluent Monitoring
- Surface Finishing
- Flocculent Coagulation
- Heavy Metal Removal and Recovery
- Toxics Destruction
- Sanitization Systems
- Pool & Spa Control
- Aquatic Animal Life Support Systems
Standards:
- CE
- Manufactured under ISO 9001 for Quality and ISO 14001 for Environmental Management
Product Details
- Manufacturer: GF Signet
- Part number: 3-2750-2
- Product type: Sensor Electronics
Review inputs, outputs, power and sensor compatibility.
| Compatible Electrodes: | Signet DryLoc® pH and ORP Electrodes Models 2724-2726, 2756-2757 Wet-Tap, 2764-2767, 2774-2777 |
|---|---|
| Operating Range pH | 0 to 14 pH |
| Operating Range ORP | ± 2,000 mV |
| Response Time pH | < 6 sec. for 95% of change |
| Response Time ORP | application dependent |
| Materials In-line | Valox® (PBT) |
| Materials submersible | CPVC |
| Cable | 4.6 m/15 ft, 3-conductor shielded 22 AWG, 100 ft max. |
| Power | 12 to 24 VDC ±10%, regulated for 4 to 20 mA output / 5 to 6.5 VDC ±5% regulated recommended, 3 mA max., for digital (S3 L) output |
| Current output pH | Fixed 4 to 20 mA, isolated, = 0 to 14 pH (custom scaling available) |
| Current output ORP | Fixed 4 to 20 mA, isolated, = -1000 to 2000 mV (custom scaling available from ± 2000 mV) |
| Max Loop Resistance | 100 Ω max. @ 12 V 325 Ω max. @ 18 V 600 Ω max. @ 24 V |
| Accuracy | ± 32 µA |
| Resolution | ± 5 µA |
| Update Rate | 0.5 seconds |
| Error indication | 3.6 mA |
| Digital (S3 L) output | Serial ASCII, TTL level 9600 bps |
| Accuracy pH | ± 0.03 pH @ 25 °C (77 °F) |
| Accuracy ORP | ± 2 mV @ 25 ° C (77 °F) |
| Resolution pH | ≤ 0.01 pH |
| Resolution ORP | 1 mV |
| Resolution Temp | ≤ 0.2 °C (32.3 °F) |
| Update Rate | 0.5 seconds |
| Available Data | Raw mV, pH or ORP, temperature (pH) |
| Error indication | Open input diagnostic |
| Input Impedance, Z | >1011Ω |
| Enclosure | 3-2750-1 & -2: NEMA 4X/IP65 with electrode connected , 3-2750-3 & -4: NEMA 6P/IP68 with electrode and watertight conduit and/ or extension pipe connected |
| Temperature (submersible) | 0 ° C to 85 ° C (32 °F to 185 °F) |
| Temperature (in-line) | 0 ° C to 110 ° C (32 °F to 230 °F) |
| Storage Temperature | -20 °C to 85 ° C (-4 °F to 185 °F) |
| Relative Humidity | 0 to 95%, non-condensing (without electrode connected) |