Specifications and Features
8900 Multi-Parameter Controller
The Signet 8900 Multi-Parameter Controller takes the concept of modularity to the extreme. Each 8900 Controller is field-commissioned with the users-specified combination of inputs, outputs, and relays using simple-to-install modular boards into the base unit. Configure the system by selecting either two, four, or six input channels which accepts any of the Signet sensors listed below, and/or other manufacturer's sensors via a 4 to 20 mA signal converter (Signet Model 8058). To complete your unit, choose a power module with universal AC line voltage or 12 to 24 VDC.
If more features are needed, analog output and relay modules are available and easily installed. Plus, the 8900 Controller will support up to four additional relays via an external relay module.
There are other notable features that the 8900 Controller offers. For example, digital input to the Signet 8900 Multi-Parameter Controller enables longer cable runs and simplified wiring with minimal noise interference. Advanced relay logic allows users to select up to three measurement sources to trigger one relay. Derived measurements include difference, sum, ratio, percent recovery, percent rejection, percent passage and BTU. The menu system can be programmed to display in multi-languages, including English, German, French, Spanish, Italian, and Portuguese.
Fields of Application:
- RO/DI System Control
- Media Filtration
- Pure Water Production
- Demineralizers
- Chemical Processing
- Metal & Plastics Finishing
- Fume scrubbers
- Proportional Chemical Addition
- Cooling Tower and Boiler Protection
- Wastewater Treatment
- Aquatic Animal Life Support Systems
- Rinse Tank
Advantages:
- Measures Flow, pH, ORP, Conductivity, Pressure, Level, Temperature and Dissolved Oxygen
- Multi-language display
- 1/4 DIN enclosure
- Up to 4 analog outputs
- Up to 8 relays
- 12 to 24 VDC or 100 to 240 VAC ±10%, regulated power
- Digital communication allows for extended cable lengths and easy wiring
- Accepts 3rd party 4 to 20 mA output devices when used with 8058 signal converter
- Available with 2 to 6 channels
- Simultaneous BTU Calculations with Heating & Cooling Totalizers per calculation
Standards:
- CE
- UL
- FCC
- RoHS compliant
- China RoHS
Product Details
- Manufacturer: GF Signet
- Part number: 3-8900-L-2-DC-4D-0
- Product type: Controller
Review inputs, outputs, power and sensor compatibility.
| Compatibility | Modular (completely field-commissionable) |
|---|---|
| No. of Input Channels | 2, 4, or 6 |
| Input Signal Types | |
| Digital (S3 L) | Serial ASCII, TTL level 9600 bps |
| Frequency | 0.5% of reading |
| Measurement Types | Flow, pH, ORP, Conductivity/Resistivity, Pressure, Temperature, Level, or 3rd party devices with a 4 to 20 mA output |
| Derived Measurements | Sum, difference, ratio, % recovery, % reject, % passage, power (BTU) |
| No. of Relays Supported | Available: 2, 4, 6 or 8 (8 dry-contact or 4 solid state and 4 dry- contact) |
| No. of Analog Outputs | Available in pairs: 2 or 4 (active and/or passive 4 to 20 mA); and/or 2 (0 to 5/10 VDC) |
| Enclosure and Display | |
| Enclosure Rating | NEMA 4X/IP65 (front face only) |
| Case Material | PBT |
| Panel Gasket | Silicone Sponge |
| Window | Self-healing polyurethane-coated polycarbonate |
| Keypad | 4-buttons, highly tactile and audible injection-molded silicone rubber seal |
| Display | Alphanumeric 2 x 16 back-lit LCD |
| Update Rate | 1 second |
| Accuracy | Sensor dependent |
| LCD Contrast | 4 settings |
| Languages Available | English, French, Spanish, German, Italian and Portuguese |
| Display Ranges | |
| pH | -2.00 to 15.00 pH |
| pH Temperature | -40 °C to 150 °C / -40 °F to 302 °F |
| ORP | -9999 to +9999 mV |
| Flow Rate | 0.0000 to 999999 units per second, minute, hour or day |
| Totalizer | 0.00 to 99999999 units |
| Conductivity | 0.0000 to 999999 μS, mS, PPM & PPB (TDS), kΩ, MΩ |
| Conductivity Temperature | -99.9 °C to 250 °C / -148 °F to 482 °F |
| Temperature | -99.9 °C to 999.9 °C / -148 °F to 999.9 °F |
| Pressure | -99.99 to 9999 psi, kPa, bar |
| Level | -99999 to 99999 m, cm, ft, in., % |
| Volume | -99999 to 999999 m³ , ft³ , in³ , cm³ , gal, L, kg, lb, % |
| Other (4 to 20 mA) | -99999 to 999999 user selectable units |
| Environmental | |
| Ambient Operating Temperature | |
| Backlit LCD | -10 °C to 55 °C / 14 °F to 131 °F |
| Storage Temperature | -15 °C to 80 °C / 5 °F to 176 °F |
| Relative Humidity | 0 to 95%, non-condensing |
| Maximum Altitude | 2,000 m (6,560 ft) 4,000 m (13,123 ft); use only DC power supply and, if applicable, solid state relays to maintain UL safety standard up to this altitude |
| Electrical | |
| Universal AC | 100 to 240 VAC ±10%, regulated 50-60 Hz, 24 VA max. |
| DC | 12 to 24 VDC, ±10%, regulated recommended, 7 Watts max. |
| Output Power to Sensors | 5 VDC up to 40 mA total |
| Terminal type | Screw-clamp, removable via plug-in modules |
| Analog Outputs (via I/O Modules and Output Modules) All analog outputs are freely assignable to any channel. | |
| 4 to 20 mA Output | Endpoints are adjustable and reversible |
| Minimum Default | 4.0 mA; user adjustable from 3.8 to 5.0 mA |
| Maximum Default | 20.00 mA; user adjustable from 19.0 to 21.0 mA |
| Test Mode | Produces an adjustable 4 to 20 mA signal for functional verification of each output circuit |
| Isolation | Up to 48 VAC/DC |
| Error Condition | 22.1 mA (default state when output source not configured) |
| Update Rate | 100 ms |
| Passive 4 to 20 mA (External Power required) Voltage | 12 to 24 VDC, ±10%, regulated |
| Active 4 to 20 mA (Internally Loop Powered) Max. Impedance | 750 Ω |
| 0 to 5/10 VDC Output | Endpoints are adjustable and reversible |
| Endpoints are adjustable and reversible | 0 to 5 VDC or 0 to 10 VDC, software selectable |
| Minimum Default | 0 VDC; user programmable from 0 to 0.5 VDC |
| Maximum Default | 5 VDC; user programmable from 4.5 to 5.5 VDC, or 9.5 to 10.5 VDC |
| Output Load | 10 kΩ minimum |
| Test Mode | Produces an adjustable signal for functional verification of each output circuit |
| Isolation | Up to 48 VAC/DC |
| Error Condition | 0 VDC (default state when output source not configured |
| Update Rate | 100 mS |
| Accuracy | ±20 mV over entire operating temperature range |
| Resolution | 5 mV |
| Power Supply Rejection | 0.5 mV/V |
| Relay Modules All relays are freely assignable to any channel. | |
| Internal relay modes of operation | Off, Low, High, Window, Proportional Pulse, Pulse Width Modulation, USP, Volumetric, |
| External relay modes of operation | Off, Low, High, Window, USP, Totalizer Volume, Advanced, % Rejection, % Recovery, % Passage |
| Hysteresis | User adjustable |
| Time Delay | 0 to 6400 seconds |
| Advanced Relay | Use "AND/OR" logic along with relay sources to trigger a relay. High/Low modes available for each of the 3 sources |
| Solid State Relays | Non-mechanical switches |
| Normally Open/Closed Operation | Software selectable |
| Maximum Voltage Rating | 30 VDC or 42 VAC p-p |
| Current Rating | 50 mA DC or 50 mA AC RMS |
| On-state Impedance | 30 Ω or less |
| Off-state Leakage | 400 nA or less, AC or DC |
| Isolation | Up to 48 VAC/DC |
| Transient Protection | Embedded, up to 48 V over-voltage |
| Dry-contact Relays | Mechanical contacts |
| Type | SPDT |
| Form | C |
| Maximum Pulse Rate | 600 pulses/min. (volumetric pulse & PWM modes). 400 pulses/min. (prop. pulse mode) |
| Maximum Voltage Rating | 30 VDC or 250 VAC |
| Current Rating | 5 A |